Analysis of Vibration Signal Caused by DC Bias at Different Measuring Points of Transformer
ID:58
Submission ID:343 View Protection:ATTENDEE
Updated Time:2021-12-03 10:33:27 Hits:629
Oral Presentation

Start Time:2021-12-17 11:15 (Asia/Shanghai)
Duration:15min
Session:[C] Power system and automation » [C6] Session 33
Video
No Permission
Presentation File
Tips: The file permissions under this presentation are only for participants. You have not logged in yet and cannot view it temporarily.
Abstract
Power transformer is easy to be invaded by the stray current of urban rail transit, resulting in DC bias. Then the DC bias will lead to severe vibration of the transformer. By analyzing the characteristics of the surface vibration signal of the transformer, whether the transformer is invaded by the stray current can be judged. In this paper, the time domain and frequency spectrum information of vibration signals of six measuring points of 220V transformer are summarized and compared. Finally, it is concluded that for the 220kV transformer, when the peak current of the neutral point changes, the vibration signal of the central point of the box surface of the intermediate phase changes most obviously. Hence, the central point of the box surface of the intermediate phase is the most suitable for measuring vibration signals caused by DC bias.
Keywords
DC bias,measuring point,transformer,vibration signal