Partial Discharge Ultrasonic Signal Detection in Transformer Bushing Based on Mach-Zehnder Fiber Optic Interferometer
ID:190
Submission ID:218 View Protection:ATTENDEE
Updated Time:2021-12-03 10:46:16 Hits:482
Oral Presentation
Start Time:2021-12-16 09:30 (Asia/Shanghai)
Duration:15min
Session:[D] High voltage and insulation technology » [D3] Session 16
Video
No Permission
Presentation File
Tips: The file permissions under this presentation are only for participants. You have not logged in yet and cannot view it temporarily.
Abstract
Oil-impregnated paper (OIP) bushings are widely used in the power system. In order to detect the weak signal generated by the partial discharge (PD) in bushing online, a fiber-optic ultrasonic sensing system based on Mach-Zehnder interference (MZI) was studied in this paper. The average sensitivity of the OFS is 67.3 dB (0 dB=1 V(m·s-1)). The performance test of the fiber-optic ultrasonic sensor (OFS) was carried out on a real 110 kV transformer bushing. PD signal was detected by the proposed MZI fiber-optic ultrasonic sensor, when the average discharge volume is 10.4 pC. The experimental results show that the interferometric fiber-optic ultrasonic sensing system can be used for transformer bushing PD ultrasonic signal detection. It is of great significance to improve the maintenance of the transformer bushing
Keywords
Partial discharge; ultrasonic; optical-fiber sensor; Mach-Zehnder interference; transformer bushing