Study on failure mechanism of oil paper insulation under partial discharge of bubble defects
ID:149
Submission ID:109 View Protection:ATTENDEE
Updated Time:2021-12-06 12:56:03
Hits:512
Oral Presentation
Start Time:2021-12-15 16:00 (Asia/Shanghai)
Duration:15min
Session:[D] High voltage and insulation technology » [D2] Session 10
Video
No Permission
Presentation File
Tips: The file permissions under this presentation are only for participants. You have not logged in yet and cannot view it temporarily.
Abstract
Partial discharge (PD) seriously affects the safe operation of power transformer. Studying the influence of PD in internal bubble of oil paper insulation and understanding the insulation failure mechanism can provide guidance for engineering practice. In this paper, the induction mechanism of PD on insulation failure is obtained by analyzing the short-time breakdown characteristics of oil paper insulation with different bubble parameters. Through the comparative analysis of bubble area and PD parameters, a positive feedback model for the insulation degradation is obtained, representing that bubble defects will deteriorate rapidly in exponential form under the effect of PD. Finally, with the help of electron microscope and energy spectrum analysis, the deterioration process of insulating paper is divided into four stages, obtaining the micro deterioration and failure mechanism of insulating paper.
Keywords
Cumulative damage,induced breakdown,oil paper insulation,partial discharge,positive feedback
Comment submit