Numerical Simulation Calculation Analysis of Very Fast Transient Overvoltage Arcing
ID:131
Submission ID:36 View Protection:ATTENDEE
Updated Time:2021-12-10 16:30:23
Hits:427
Poster Presentation
Start Time:2021-12-17 14:35 (Asia/Shanghai)
Duration:5min
Session:[Z] Poster Session » [Z4] Poster Session 4: High voltage and insulation technology
Video
No Permission
Presentation File
Tips: The file permissions under this presentation are only for participants. You have not logged in yet and cannot view it temporarily.
Abstract
In gas insulated substation (GIS), very fast transient over-voltage (VFTO) is caused during the switching operation because of repeated arc reignition. At present only the first arc is considered for numerical simulation of VFTO, which can’t describe the character of VFTO exactly, because the time of arc reignition and extinction is difficult to determine. Base on arc dynamic energy equation, the paper confirms the decision condition of arc reignition and extinction, and gets VFTO wave and peak voltage of each node during arc reignition by simulating. Comparing to the two results, it could see that, for the same node, there was not great change in wave forms; the VFTO maximums both on mains side of switching, also this node’s peak voltage had the largest difference, base on the first arc peak voltage, approximately 10.78%, which should been attention to for insulation of apparatus.
Keywords
GIS; Very fast transient over-voltage; Breakdown voltage of dielectrics; Arc reignition