Identification Method of Negative and Weak Damping Generator Sets Based on TLS-ESPRIT and Damping Torque Analysis
ID:119
Submission ID:245 View Protection:ATTENDEE
Updated Time:2021-12-03 10:39:51 Hits:428
Oral Presentation
Start Time:2021-12-16 11:15 (Asia/Shanghai)
Duration:15min
Session:[C] Power system and automation » [C4] Session 21
Video
No Permission
Presentation File
Tips: The file permissions under this presentation are only for participants. You have not logged in yet and cannot view it temporarily.
Abstract
Aiming at the ultra-low frequency oscillation or low frequency phenomenon in power system, it is necessary to identify the negative or weak damping gensets which cause the oscillation accurately to formulate control measures ensuring the safe and stable operation of power grid. Therefore, this paper proposes an effective identification method based on a total least squares-estimation of signal parameters via rotational invariance techniques (TLS-ESPRIT) and damping torque analysis (DTA). In this method, firstly the dominant oscillation mode of each generator is extracted from measured signals (e.g. rotor speed, rotor angle, and active power) at its side by means of TLS-ESPRIT, and then corresponding damping torque coefficient can be obtained through the least square fitting method to determine whether the generator is the oscillation source of this oscillation mode. Finally, case studies are carried out on the 4-machine 2-area system. Simulation results indicate that the proposed method can accurately identify the native damping units.